>>aircon not cold>>warm Fundamental Concept: When it feels warm while your hand is placed right at the outlet, it means, the air conditioner is not producing cold air at all. It cold be due to: a) a faulty indoor pcb that doesn't send a request to the condenser, or b) the condenser receives a signal from the indoor unit, but is not processing it, or c) a faulty starting capacitor that doesn't kick start the compressor, or d) a compressor that runs out of gas (gas leak), or e) a faulty compressor, or f) the compressor has overheated and shut down, or g) the outdoor fan motor is jammed or spoilt, or h) the outdoor condenser is choked Remarks: When an air conditioner is not producing cool air, it can be caused by a number of factors. Most people jump to the conclusion that it has run out of gas. Nevertheless, this is the least probable of all. Ranked highest is in fact: "c) a faulty starting capacitor that doesn't kick start the compressor" for a non-inverter system Nevertheless, we will guide you step by step to help you streamline what exactly had gone wrong. Systematic Troubleshooting : Step 1: Please confirm if your remote controller is set to the COOL mode, or represented by the snow flake symbol, not fan nor dry: COOL FAN DRY Step 2: Can you see the front of the condenser? Is the fan turning? Note: if you cannot see the front of the condenser, take a piece of paper and put it on the condenser fan coil;if the fan is turning, it will suck the paper towards it. Is the fan turning? Yes No |